Smart-UPS VT 10KVA 400V with 2 Batt Module
OUTPUT POWER CAPACITY: 8000 Watts / 10 kVA NOMINAL VOLTAGE: Output: 230V, 400V 3PH; Input: 400V 3PH OUTPUT VOLTAGE NOTE: Config for 380:400 or 415 V 3Phase nominal O/P voltage INPUT VOLTAGE: Range for main operations 304 - 477V Other Input Voltages 380,415 MAXIMUM INPUT CURRENT: 14A; INPUT BREAKER CAPACITY: 20A CONNECTIONS: Output : (1) Hard Wire 4-wire (3PH + G) (1) Hard Wire 5-wire (3PH + N + G) (1) Screw Terminals Input : Hard Wire 5-wire (3PH + N + G) BYPASS : Built-in Maintenance Bypass, Built-in Static Bypass INTERFACE : DB-9 RS-232, Smart-Slot BATTERY TYPE: Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof TYPICAL RECHARGE TIME: 5 hour(s) INCL BATT MODULES: 2; AVAILABLE BATT SLOT: 0 TYPICAL BACKUP TIME: At Half Load: 46.5 minutes (4000 Watts) At Full Load: 18.5 minutes (8000 Watts) CONTROL PANEL: Multi-function LCD status and control console AUDIBLE ALARM: Audible and visible alarms : configurable delays MAX DIM: 1490 x 352 x 838 mm (HxWxD); COLOR: Black * Includes 5X8 start up service * Parallel-capacity capable; * Parallel-redundant capable. | ||
|